21 2019Maintenance & Service Schedule For Diesel Generator
Daily service For Generator Set
· Check the instrument panel
· Check the coolant level of the cooling system
· Check the maintenance indicator of the engine air filter and clean if necessary
· Check the engine oil level
· Drain off the water and deposits in the fuel tank and oil-water separator
· Check the functioning of the coolant heater
· Check the engine
Service after the first 250 hours of operation For Generating Set
· Check the engine valve clearance and adjust if necessary
· Clean and test the magnetic speed sensor
· Replace the lubricant and filter
· Replace the coolant filter
· Clean and / or replace the fuel filter
Service for every week or every 50 hours of operation
· Check the air filter
· Drain off the water in the oil-water separator
· Check the level of the battery electrolyte
· Check the engine oil level
· Check the coolant level
· Check the engine exhaust piping
· Check the fuel supply system
· Check the electrical connection
· Check the sensors and alarm output to ensure their reliability
Service for every month or every 100 hours of operation FOR dg Set
· Check the air intake and exhaust systems to ensure they are not obstructed
· Check for any leakage of the engine exhaust system
· Check the tension of the V-belt
· Check voltage and electrolyte specific gravity of the battery
· Check the battery charger
· Check the reliable functioning of the ATS transfer switch
· Check the output voltage and frequency of the generator
· Drain off the condensate water in the engine exhaust system
· Drain off the water in the oil-water separator
· Test the load-carrying capacity of the genset
Service for every 250 hours of operation
· Add anti-corrosion additive into the cooling system
· Lubricate the drive bearing of the fan
· Check the hose and fasteners of the engine radiator
· Clean the radiator
· Replace the lubricant and filter
· Replace the coolant filter
· Clean and / or replace the fuel filter
Service for every 6 months or every 500 hours of operation
· Replace the air filter
· Check the anti-freezing fluid
· Check the tension of the V-belt
· Check the insulation and fire-proofing devices
· Check the electric circuit
· Check the tightness of bolts, screws and parts subject to vibration
· Check and adjust the engine valve clearance
· Check and adjust the injection advance angle
· Drain away the deposits in the main fuel tank
· Clean the battery terminals
· Clean the rotor and stator of the generator with compresses air
Service for every year or every 1000~2000 hours of operation
· Replace the coolant
· Replace the oil-water separator
· Replace the engine oil and oil filter
· Replace the fuel filter
· Clean the vent of the engine crankcase
· Adjust and tighten any loose parts
· Check and adjust the valve clearance
· Check and adjust the injection advance angle
· Check the turbocharger
· check the fuel injection pump and water pump
· Check the transmission mechanism and corresponding phase
· Check the genset protections
· Check and adjust the magnetic speed sensor
· Check the winding and electrical connection
· Measure the insulation resistance
Service for every 2 years or every 2000~3000 hours of operation
· Check the crankshaft vibration damper
· Replace the coolant and clean the cooling system
· Conduct the load-carrying capability test